The Offline Clause That Moves Charging Authority Into the Depot
A fleet charging limit must remain enforceable after the connection to its coordinator disappears. Otherwise, peak shaving lasts only as long as the communications path, while the transformer continues carrying every vehicle that can still draw power. The implementation question is where the binding limit resides and what authority survives the outage.
The clause changes the control boundary
For charging control interoperability, the relevant standards family is the Open Charge Point Protocol, whose smart charging provisions describe how stations apply centrally supplied schedules. In OCPP 1.6, the normative clause on offline smart charging requires a station with a transaction profile to continue using it for that transaction, and requires available profiles to govern when no transaction profile has been received. It also permits the decisive exposure: without installed profiles, an offline transaction proceeds without profile constraints, although equipment limits still apply, as specified in the Open Charge Alliance specification. This changes the implementation from a coordinator that repeatedly requests lower consumption into a station that already holds enforceable constraints before communication disappears. The protocol behavior establishes interoperability, while the depot designer must establish that the surviving constraints protect the shared supply.
A default is not a transformer guarantee
An offline default protects the transformer only when the combined demand permitted across all stations, together with the reserved demand of other depot loads, fits the electrical envelope under the same outage.
Keep the binding ceiling below the optimizer
Consider a design requirement that limits charging demand to 200 kW at the depot supply boundary, with conversion losses included in that accounting. Partition this budget into locally enforceable station ceilings, then let the fleet optimizer allocate energy within those ceilings according to departure commitments and vehicle acceptance limits. A default transaction profile alone is insufficient as the architectural boundary because transaction scheduling can replace default behavior, so the binding station ceiling must remain effective independently of whichever transaction schedule applies. The aggregate power budget also needs a separate engineering check against phase loading, reactive demand and transformer thermal headroom, since active power alone does not establish winding protection. Apply this decision rule: permit continued charging during coordinator loss only when the station can enforce an allocation whose aggregate remains within the reserved site envelope for the full disconnected interval. Permanently conservative allocations sacrifice utilization, while dynamically transferable allocations require an authority handover that prevents the old and new recipients from spending the same capacity.
Prove the surviving authority
The compliance evidence should trace the offline requirement to stored configuration, local enforcement and measured supply behavior, with loss of the coordinator connection as the injected failure. Disconnect that connection while vehicles are requesting energy, repeat the exercise with an offline transaction start where authorization permits it, and retain the installed profiles, effective schedules, station events and synchronized electrical measurements. Exercise schedule boundaries during the same outage, because a limit that expires while the coordinator is unreachable cannot support a claim of continued containment. On reconnection, reconcile the allocations still enforced locally before allowing the optimizer to redistribute capacity, and demonstrate that restoration does not briefly authorize overlapping allocations. Approval of degraded operation therefore depends on measured containment and explicit service consequences: the fleet operator must decide which departure commitments can slip when the surviving local allocations leave usable transformer capacity stranded.